ASC ECOMAX-T
Notification Leds
+ Leakage - : At any contact between (+)polarity-earth in DC supply, the LED become active.
Leakage High : At any contact between (-)polarity-earth in DC supply, the LED become active.
Temperature: When the internal temperature of the rectifier reaches the temperature value in the settings, the LED become active.
Low Temperature : As soon as the rectifier internal temperature reaches the factory set 5 cfc, the LED becomes active.
DC High : When the output of the rectifier reaches the DC High value in the settings, the LED becomes active.
DC Low : When the output of the rectifier reaches the DC Low value in the settings, the LED becomes active.
AC High : When the AC voltage reaches the AC High value in the rectifier settings, the LED becomes active.
AC Low : When the AC voltage reaches the AC Low value in the rectifier settings, the LED becomes active.
AC ON: LED is active when AC input supply is at nominal value.
Over Load: When the DC output on the rectifier exceeds the total current value, the LED becomes active.
Current Limitation: When the battery output on the rectifier reaches the battery charging current value in the settings section, the LEDs becomes active and the rectifier starts to work in current limiting mode.
Battery Critical : When the battery voltage reaches below the battery alarm value in the setting,LED becomes active.
RTC Battery Low: There is an RTC on the rectifier. When the device is de-energized, RTC works with the battery it is connected to. When the voltage of the battery drops below the factory set value, LED is activated.
Battery Alarm: If Y is selected in the Battery Fail Y/N section in the rectifier setup menu and the battery voltages fall below the DC voltage set in the Battery Fail(v) section, the LED will be active.
Normal Charge: When the rectifier is working in Normal Charge mode, the LED is active.
Boost Charge: When the rectifier is working in Boost Charge mode, the LED is active.
Batt.Reverse Con.: When the battery group is connected to the rectifier reversely, the LED is active.
Buttons
PRG/ESC Button : It is used for to enter the setting menu of the rectifier and communication,event records, clock settings and to exit the warning section.
SET Button : It is used to change the value by pressing the up or down buttons together with the set button if any change is desired in the setting menu of the rectifier.
Up Button : It is used for page transitions of the rectifier, navigating the event logs and changing the values in the setting part.
Down Button : It is used for page transitions of the rectifier, navigating the event logs and changing the values in the setting part.
BOOST Button : It is used for the rectifier to pass fast charging mode manually.
NORMAL Button : It is used to manually switch the rectifier to boost charge mode.