ASC 1110XX Series DC Supply System / Rectifier

1110XX is the DC Supply system, is used for to supply DC to Scada, measurement, protection and MV Switching Equipments in OG Switching Centers.

  • DC Output Voltage Low
  • DC Output Voltage High
  • AC Input Voltage Low
  • AC Input Voltage High
  • Earth (+, -) Leakage Alarm
  • Battery Alarm
  • Temperature and Fan Alarm
  • Short Cirucit Alarm
  • AC On Alarm

*Above notifications can be monitored and transmitted via dry contacts.

For suitable charging of the batteries, ASC 1110XX series are designed with current and voltage regulators.

12V Nominal voltage, 6 cells VRLA type batteries are included in the system and are deep discharge proof. They set to 2,23V for each cell and the output voltage for 54 cells is 121,0V.

Thanks to its compact design, Removing and installation of batteries much more easier and reqires less time than before.

To provide DC rectify voltage and isolate the protection system from the network in terms of 2kV 5mA, ASC 1110XX has a powerfull transformer whish has copper wire and “H” class temperature values.

Thanks to its design, hardware and high quality equipments, ASC 1110XX series prevents wrong trips, circuit breaker explosions, relay damages and also reduces the labor costs.

 

To charge the batteries in most suitable way and extend their life time, ASC 1110XX is designed with current and voltage regulators and automatic battery maintenance function. The ripple voltage is <%5 without battery and <%1 with Battery.

ASC 1110XX series are available from 5 to 100A in single-phase input configuration with offering output voltage 110Vdc. (please see other ASC series for there-phase input configuration and different output voltages)

Thanks to our own R&D department, all electronical and mechanical designs are carried out by ourselves for improved reliability and adaptability to industrial requirements.

ASC 1110XX series have easy to use HMI for quick on-site adjustments. Please see the below pages for parameter settings.

ASC 1110XX series can be manufacture according to your special requirements.

Please get in touch with us for the special requirements and optional moduels below.

- 0 -10V / 4-20mA Informations Transmitting Module
- Digital Fan Control Module
- Deep Discharge Protection Module
- Surge Arrester Protecion Module
- Modbus Communication Module
- Battery Capacity Selection Module

 

  • SCR Based Microprocessor, Wide Graphical LCD Control Panel
  • Low Ripple Voltage
  • Scada Compatible (MODBUS Optional)
  • Automatic Battery Maintenance, Long Life Batteries
  • Stable Output Voltage, Perfect Discharge Curves
  • No gas generates during bosst charging
  • 0 -10V/4-20m Information Transmitting (Optional)
  • Digital Fan Control (Optional)
  • Deep Discharge Protection Module (Optional)
  • Surge Arrester Protecion (Optional)
  • Battery Capacity Selection and automatic charging setting (Optional)

Optional Intelligent VRLA Battery monitoring system is avaliable for analyzing SOH of Block battery, SOC of String battery, Curve Trend analysis, Bar Graph report and Threshold Alarm. ASC 1110XX series are able to measure Block Battery’ s Voltage, Temperature and Inner resistant (ohm).

- For different charging current and battery capacity please get in touch with us.
- Dimension may vary depening on the optional modules, charging current and battery capactiy.
- Weight may change depending on the optional moduels, charging current and battery capactiy.
- Please check the dimensions and weight after ordering the optional modules, different charging current or battery capacity.

ASC 1110XX Series can able to give warnings according to the set parameters via LED’s, audible and visual
DC Leakage Led: LED will be on, If there is a DC leakage on the system.
Battery Failure Led: LED will be on, If any of the batteries have problem.
AC High Led: LED will be on, If AC is higher than the set value.
AC Low Led: LED will be on, If AC is lower than the set value.
DC High Led: LED will be on, If DC is higher than the set value.
DC Low Led: LED will be on, If DC is lower than the set value.
Battery Alarm Led: LED will be on, If any of the batteries have problem.
AC On Led: LED will be off, If there is no AC on the charger or any internal failure.
- ASC 1110XX Series, included a service port for further upgrades in case of additional system requirements.
- ASC 1110XX Series, included a PRG/ESC button to reach the settings.
- ASC 1110XX Series, included a SET button, to change the settings.
- ASC 1110XX Series, included directional pads to sweep inside the settings.
- ASC 1110XX Series, included a mute button, to avoid the audible alarm.

 

We are ready to be your energy