Sıa-B Specific Ct's - Dual & Self-Powered Oc&Ef Protectıon Relays
This adaptation of the SIA-B relays offer reduced dimensions, making this relay easy to install, and its lightweight helps the customer to save costs in transport.
The protection relay offers the advantage in self-powered mode, SIA-B starts up from 0.4 times the minimum primary current of the CT (three-phase current).
SIA-B is suitable for RMUs, SF6 insulated, and compact switchgear in those installations where the space is critical, making the maintenance much more manageable.
USB front port connection (ModBus RTU protocol) for local communication. Remote communication through rear RS485 (ModBus RTU)
The relay is self-powered using the operating current through three specific current transformers fitted on the lines. These transformers are also used to obtain current measurements. Besides, SIA-B can be used with an auxiliary power supply (24-230Vac/dc). The relay can be also supplied by a USB cable connected to the laptop, with the USB KITCOM adapter or a standard power bank.
The SIA-B, Self-powered Protection Relays fits perfectly in EATON Xiria SF6Free medium voltage switchgear and requires minimal inspection, and maintenance leading to low operation costs.
Fanox SIA-B is a great addition to Xiria offering and creating more versatility for its growing customer base. This cooperation benefits the end-users. It can be used for more demanding applications; photovoltaic, windfarm, renewable energy.
The SIA-B is an OC&EF protection relay with self-powered and dual-powered (self-powering + auxiliary power) options.
• The relay is self-powered using the operating current through three specific current transformers fitted on the lines. These transformers are also used to obtain current measurements. Besides, SIA-B can be used with an auxiliary power supply (24-230Vac/dc). The relay can be also supplied by a USB cable connected to the laptop, with the USB KITCOM adapter or a standard power bank.
• Internal commissioning battery included (Lithium battery: 20 years lifetime), as optional.
• Metallic box with high electromagnetic compatibility level (EMC) and wide range of operating temperature.
• In self-powered mode, SIA-B starts-up from 0.4 times the minimum primary current of the CT (three-phase current).
• Test menu allows the trip circuit to be tested before the transformation centre is powered up.
• Bistable magnetic indicator (flag) which indicates the trip condition, maintaining its position even though the relay loses the supply.
• Self-diagnosis of the relay status (WATCHDOG) through a LED.
• Low power consumption.
• To allow communication, relays are provided with a local micro USB front port and with optional remote communication RS485 port (Modbus RTU protocol) on the rear side.
• The SIA-B is provided with a trip output for low power coil (24 Vdc – 135 mJ) and depending on the model, 1 external trip input and 2 configurable outputs.
• The SIA-B is provided with non-volatile RAM memory in order to store up to 100 events and disturbance fault recording (DFR – 4 fault reports in data format), maintaining date & time thanks to its internal RTC (Real Time Clock) even without power supply.
• The installation and subsequent maintenance of external batteries are eliminated. The operating costs of the centre are reduced.
• Its compact size makes SIA-B easy to install and its lightweight helps the customer to save costs in transport.
50 Instantaneous phase overcurrent
51 Inverse time overcurrent
51N Inverse time calculated neutral overcurrent
49T External trip
50N Instantaneous calcalated neutral overcurrent
49 Thermal image
49T External trip
PGC Programmable logic control
TB Trip Block for switch disconnector
Communication Software for SIA & SIL protection relays
The SICom PC software has been designed and programmed to gain access to all of Fanox relays information, to modify the settings and configuration, check states and measurements and to analyse and save events and fault reports using a graphic-friendly user interface.
SICom software works with the Windows® Windows 7, Windows 8, Windows 8.1 and Windows 10 operating system.
- General data reading: Complete model, Version, Serial number, etc.
- States reading
- Measurements reading
- Reading and changing settings
- Reading and changing configuration
- Reading and deleting events
- Reading and deleting fault reports
- Reading and deleting demand current (load data profiling)
- Reading and saving oscillographic records in Comtrade format
- Changing the user passwords
- Saving and Loading settings files
- Saving and Loading configuration files
- Saving events and fault reports
- Saving demand current (load data profiling)
- Date-time synchronization
- Configuring the communication parameters
- Reading and changing counters
- Commands for opening and closing the circuit breaker and block/unblock the recloser
- Configuration of the inputs
- Configuration of the outputs
- Configuration of the causes that start a Fault Report
The update of the software does not require any user´s action, this is, if the computer is connected to Internet, SICom updates itself when it is started.
It will allow you to prepare all the settings and relay configurations without having the relay connected to the PC (offline mode), reducing engineering and commissioning time.
SICom program uses Modbus protocol, so only the ports with this protocol can be used to establish the communication.
Taped CT for SIA-B Dual & Self Powered Relay – CT-MTP Taped
Battery Power Supply – KITCOM
Striker – PRT
Trip Coil Module – TCM
Epoxy resin CT for SIA-B Dual & Self Powered Relay – CT-MTP Epoxy
SIA-B SPECIFIC CT'S | SIA-B STANDARD CT'S | SIA-C STANDARD CT'S | SIA-F | |
---|---|---|---|---|
TYPE | SELF & DUAL POWERED (SELF+AUX) | SELF & DUAL POWERED (SELF+AUX) | SELF & DUAL POWERED (SELF+AUX) | AUXILIARY POWERED |
Auxiliary Supply | 24-230 Vac/dc | 24-230 Vac/dc | 24Vdc230Vac48 Vdc110-230 Vac/Vdc | 24-220 Vcc / 48-230 Vac |
Self Power Supply | I > 0,35 x Is min (x3) | 0,075 In (x3) | 0,1 In (x3) | |
External battery | USB cable / Power bank | USB cable / Power bank | KITCOM | USB cable / Power bank |
Internal battery | √ (*) | √ | √ (*) | |
Consumption | 0,5 W | 1,5 W | 0,5 W | 1,5 – 2,2 W |
CT | Specific CT | Standard CT/1A - 2VA | Standard CT/1A - 2.5VA Standard CT/5A - 5VA | Standard CT/1 - 0,5VA Standard CT/5A - 0.5VA |
50 | 1 | 2 | 2 | 1 |
50G | 2 | 2 | 1 | |
50N | 1 | |||
51 | 1 | 1 | 1 | 1 |
51G | 1 | 1 | 1 | |
51N | 1 | |||
SHB | 1 | 1 | 1 | |
74CT | 1 | |||
46BC | 1 | |||
46 | 1 | 1 | ||
79 | 1 | |||
52 | 1 | 1 | 1 | |
50BF | 1 | 1 | 1 | |
49 | 1 | 1 | 1 | 1 |
49T | 1 | 1 | 1 | 1 |
CLP | 1 | 1 | 1 | |
74TCS | 1 | |||
Trip Block | 1 | 1 | 1 | |
68 Zone Selection interbloking | 1 | 1 | 1 | |
86 | √ | √ | √ | |
PGCProgrammable Logic | V3 | V3 | V3 | V3 |
Counters | √ | √ | √ | |
Commands | √ | √ | √ | √ |
Sett. Group | 2 | 4 | 3/4 | 3 |
Inputs | --- EXT.TRIP | 3 DI | --- EXT.TRIP 2DI 2DI + EXT.TRIP | --- 2DI |
Outputs | --- 2NC-NO | 3 NC-NO | --- 2 NC-NO 3 NO | 1 NO + 2 NC-NO |
Output for STRIKER | 24 Vdc – 135 mJ | 24 Vdc – 135 mJ | 24 Vdc – 135 mJ | |
LEDs | 2 LEDs 2 LEDs +1MAG.FLAG | 4 LEDs | 3 LEDs + 1 MAG.FLAGS 3 LEDs + 3 MAG.FLAGS | 3 LEDs configurable |
HMI | 20x2 LCD + 7/8 keys | 20x2 LCD + 8 keys | 20x2 LCD + 7/8 keys | 20x2 LCD + 7 keys |
Event | 100 | 1024 | 1024 | 200 |
Fault Report | 4 | 20 | 20 | 4 |
Oscillography | 10 records x 50 cycles | 10 records x 50 cycles | 1 record x 22 cycles | |
Current demand | √ | √ | ||
Local Port (frontal) | Micro USB | Micro USB | RS232 Micro USB | Micro USB |
Remote Port (rear) | RS485 | RS485 | RS485 | RS485 |
Communications Protocols | ModBus RTU | ModBus RTU ModBus RTU or DNP3.0 | ModBus RTU ModBus RTU or IEC60870-5-103 | ModBus RTU DNP3.0 |
Size of (HxW) | Vertical: 120,65 x 167,80 mmHorizontal: 185,80 x 102,7 mm | 90 x 245 mm | Vertical Compact: 177 x 155 mmVertical Standard: 177 x 189 mmHorizontal: 177,8 x 290,3 mm | 167,80 x 120,65 mm |