RIK 322 and RIK242 ANNOUNCIATOR RELAYS
RIK-322 and RIK-242 is used for observing the alarms with the help of led indicators which occurs in several applications, taking records with real time and monitoring remotely with RS-485.
- 24-32 channel signal input
- Double colored backlighted indicator
- Assigning the channels to “HORN” and “ALARM” relays seperately with the help of dipswitches.
- Designation of green indicates “HORN” channels and red indicates “ALARM”channels.
- Isolated RS-485 port
- Standard MODBUS RTU protocol
- Lithium battery supported real time clock( at least 5 years lifetime battery)
- Able to hold 3000 record with real time.
- 24V,48V,110V and 220V DC signal input
- Alarm detection mode with respect to presence or absence of the signal.
- Alarm detection mode with 0-30sec ranged adjustable delay
- Two kind of working mode: “CONTINOUS” and “PULSE”
- Validation, rubbing of an alarm and testing the indicators with the buttons on the front panel
- Alarm warning with a buzzer
- Two pcs. of relay output as “HORN” and “ALARM”
- Configuration with dipswitch
- Adjustable mode as “ANC” and LSK”
- According to instuctions in the user manual, montage and connections should made by the authorized persons. Do not turn on the device unless a proper connection is established.
- Be sure that the device is de-energized before connecting the device to the line.
- Use dry cloth to clean/remove dust from the device. Don’t use any corrosive material like alcohol and thinner.
- Put the device into use after all connections are completed.
- Don’t open the device box. There is no part exist that the user make any changes on it.
- Keep the device away from the humid, wet, vibrant and dusty ambients.
SIGNAL INPUT
There is 32 led incdicators on this device. These indicators are assigned to related signal input channels. When alarm occur on a channel, related indicator specifies that case of alarm. Led indicators can be lit double colored as red and green. Besides depending on continuity of the signals on the input channels and occurance of the alarm as first or last, flashing mode of the leds can vary.
Front Panel Buttons
There are four pieces of buttons situated on the front panel of the device:”HORN”, “ACK”, “DEL” and “TEST”
HORN: This button turns off the buzzer if the buzzer is active.
ACK: This button is used for approving the alarm. When the ACK button is pressed, if the signal situation continuous, fast flashing leds becomes to flash slowly and slow flashing led indicators keep its positions. If the signal situation is not continuous, ralted led indicators lits constant(not flashing).(In LSK mode, this button deactivates the relays but as long as alarm input is active, leds keep to continue litting which belongs to that input channel).
DEL: This button is used for deleting the alarms. When DEL button is pressed, related channels indicators are dimmed if alarms on the channels are approved and signal situation stops.
TEST: This button is used for controlling the device and led indicators are working correctly. As long as TEST button is pressed, led indicators lits as red and green respectively.
Alarm/Horn Status and Relays
All input channels can be adjusted separately as “ALARM” and “HORN” channel with dipswitches.
Red led indicator is assigned to “ALARM” channels and green led indicator is assigned to “HORN”channels.
Two relay present in the device as “ALARM” and “HORN”. Alarm channels are assigned to the “ALARM” relay and horn channels are assigned to “HORN” relay.
In LSK mode, as long as the channel input is active, device will give output at the end of the delay time.